LearnSCADAIEC 61850

IEC 61850 MMS and Ignition

SCADA station bus · Ethernet Relayfeeder 1 Relaytransformer Meterbus

MODBUS

40001

a register: you look up what it means

IEC 61850

XCBR1.Pos

a model: the name says what it is

IED relay · bay controller · meter └ Logical device LD0, CTRL, PROT └ Logical nodes the building blocks
XswitchgearXCBR circuit breaker
MmeteringMMXU measurements
PprotectionPTOC time overcurrent
CcontrolCSWI switch controller
IED1LD0
device
/XCBR1
logical node
.Pos
data object
.stVal
attribute
MMXU1
measurements
.PhV
phase voltage
.phsA
phase A
.cVal.mag.f
magnitude, float
the same structure on every vendor's relay
STstatus
MXmeasured
COcontrol
CFconfig
SPsetpoints

q

quality

good · invalid · questionable
plus flags such as test mode

t

timestamp

set by the IED when the value changed,
not when someone read it

SCADA MMS client Relay MMS server MMS · TCP 102 read values · reports · operate
MMSstation bus
SCADA to IEDs
GOOSEmulticast, relay to relay
trips in milliseconds
Sampled Valuesprocess bus
from merging units

DATA SET

XCBR1.Pos.stVal
XCBR1.Pos.q
XCBR1.Pos.t
MMXU1.PhV.phsA
PTOC1.Op.general
data change
quality change
integrity period
general interrogation

Unbuffered reports

sent only while a client is connected

Buffered reports

held in the IED through a lost connection, delivered in order

ICDwhat an IED
can do
CIDone IED,
configured
SCDthe whole substation: IEDs,
data sets, reports, addresses
Ignition IEC 61850 driver · built in
Since 8.1.25no extra cost
MMS clienteach relay is a server
Triangle MicroWorks61850 library
Windows · Linux x64Visual C++ runtime

DEVICE CONNECTION · IEC 61850

Hostname10.10.1.21
Port102
Use SCD File✓ substation.scd
IED NameIED1
IED1 └ LD0 └ XCBR1 └ Pos ├ stVal ├ q └ t
LD0/XCBR1.Pos.stVal
valueclosed
qualityGood
timestampIED time

Report folder

subscribe in the Designer's tag browser

Limited RCBs

an IED has only so many report control blocks

One report control block, one connection at a time
UDT · XCBRPos.stVal
Pos.q · Pos.t
Pos.ctlVal
Breaker 52-1closed
Breaker 52-2closed
Breaker 52-3open
Feeder meter · MMXU
Selectclient
→
ConfirmIED
→
Operateclient
1direct operate2 · 4select before operateno writes from the Quick Client
Check = 00

The IED ignores interlocking (CILO) and synchrocheck (RSYN), and executes anyway.

Test every control against a simulator, and again at factory acceptance.

Protection

GOOSE and Sampled Values, between relays and merging units

The HMI

on the station bus, reading reports over MMS

The data modelIED · logical nodes · attributes · q and t
CommunicationMMS · GOOSE · SV · reports · SCL
In Ignitionnative MMS driver · SCD · tags · UDTs · controls
IEC 61850 + Ignition
The substation, on your screens
learnscada.com